DQR ID | Subject | Data Streams Affected | Data Quality Metric |
---|---|---|---|
D080313.1 | SGP/ECOR/E24 - Water Vapor Density Incorrect | sgp30ecorE24.b1 | Suspect |
D080428.1 | SGP/ECOR/E24 - Half Hours of Data Missing | sgp30ecorE24.b1 | Does not affect quality |
Start Date | Start Time | End Date | End Time | Data Quality Metric |
---|---|---|---|---|
03/01/2008 | 0000 | 04/12/2008 | 0230 | Suspect |
Subject: | SGP/ECOR/E24 - Water Vapor Density Incorrect |
DataStreams: | sgp30ecorE24.b1 |
Description: | Mean Water Vapor Density (mean_q) often did not trend well with the co-located SMOS and sometimes jumped downwards approximately 200 to 300 mmol/m^3. Some of the instances were clearly a result of contamination by precipitation, but others were not; the latent heat flux was sometimes affected. It was determined that all instances of this behavior from the beginning of 2008 through the beginning date of this DQR were caused by precipitation/dew/frost. |
Measurements: | sgp30ecorE24.b1:
|
Start Date | Start Time | End Date | End Time | Data Quality Metric |
---|---|---|---|---|
10/27/2006 | 0530 | 11/08/2007 | 1600 | Does not affect quality |
Subject: | SGP/ECOR/E24 - Half Hours of Data Missing |
DataStreams: | sgp30ecorE24.b1 |
Description: | Individual half hours of data were missing infrequently because of a UPS problem. The extent of missing data is minimal, with only a few to several half hours missing most months. Data quality of the surrounding data times was not affected. |
Measurements: | sgp30ecorE24.b1:
|