Start Date | Start Time | End Date | End Time | Data Quality Metric |
---|---|---|---|---|
11/11/2012 | 0750 | 02/08/2013 | 1525 | Does not affect quality |
Subject: | SGP/IRT/C1 - 10m IRT ground surface temperature |
DataStreams: | sgpirt10mC1.b1 |
Description: | The 10m IRT was measuring lower ground surface temperature than the 25m IRT. The lens was cleaned on 12/19/2012 and replaced on 2/8/2013 but the difference in temperature appears to be due to the seasonal difference in surface cover - tall grass vesus bare soil. |
Suggestions: | |
Measurements: | sgpirt10mC1.b1: more
|