Data Quality Reports for Session: 118703 User: lindsay1m1 Completed: 04/06/2009


TABLE OF CONTENTS

DQR IDSubjectData Streams Affected
D040608.6SGP/EBBR/E13 - Automatic Exchange Mechanism Failuresgp15ebbrE13.b1, sgp30ebbrE13.b1, sgp5ebbrE13.b1
D040915.2SGP/EBBR/E13 - Net Radiation Incorrect, Fluxes Incorrectsgp15ebbrE13.b1, sgp30ebbrE13.b1, sgp5ebbrE13.b1
D040915.6SGP/EBBR/E13 - AEM Failure, Fluxes Incorrectsgp15ebbrE13.b1, sgp30ebbrE13.b1, sgp5ebbrE13.b1
D050624.7SGP/EBBR/E13 - Improved EBBR CR10 Programsgp30ebbrE13.b1
D051111.11SGP/EBBR/E13 - metadata correctionssgp15ebbrE13.b1, sgp30ebbrE13.b1, sgp5ebbrE13.b1


DQRID : D040608.6
Start DateStart TimeEnd DateEnd Time
06/05/2004013007/14/20041515
Subject:
SGP/EBBR/E13 - Automatic Exchange Mechanism Failure
DataStreams:sgp15ebbrE13.b1, sgp30ebbrE13.b1, sgp5ebbrE13.b1
Description:
The AEM was stuck in the home_15 position or reported near zero
home signals during much of the indicated period.

The Bowen ratio and latent and sensible heat fluxes were incorrect 
when the AEM was not operating properly; the periods of incorrect
data can be determined from the home signal values.

On 7/14/04 the AEM was replaced.
Measurements:sgp15ebbrE13.b1:
  • Left air temperature(tair_l)
  • Right air temperature(tair_r)

sgp5ebbrE13.b1:
  • Temperature of bottom humidity sensor chamber(thum_bot)
  • top vapor pressure(vp_top)
  • top air temperature(tair_top)
  • Temperature of the top humidity chamber(thum_top)
  • bottom vapor pressure(vp_bot)
  • Bottom humidity(hum_bot)
  • Top humidity(hum_top)
  • bottom air temperature(tair_bot)

sgp30ebbrE13.b1:
  • Bottom humidity(hum_bot)
  • ratio of sensible/latent heat fluxes (Bowen ratio)(bowen)
  • bottom vapor pressure(vp_bot)
  • Temperature of bottom humidity sensor chamber(thum_bot)
  • Temperature of the top humidity chamber(thum_top)
  • latent heat flux(e)
  • h(h)
  • bottom air temperature(tair_bot)
  • top air temperature(tair_top)
  • Top humidity(hum_top)
  • top vapor pressure(vp_top)


Back To Table of Contents

DQRID : D040915.2
Start DateStart TimeEnd DateEnd Time
08/11/2004023008/11/20041824
Subject:
SGP/EBBR/E13 - Net Radiation Incorrect, Fluxes Incorrect
DataStreams:sgp15ebbrE13.b1, sgp30ebbrE13.b1, sgp5ebbrE13.b1
Description:
Rain entered the net radiometer through a crack in the upper dome and
settled in the bottom dome.  This caused too large net radiation measurements
during the following daylight hours, until the domes were replaced and dried out the same 
day.
Measurements:sgp15ebbrE13.b1:
  • Net radiation(mv_q)

sgp5ebbrE13.b1:
  • net radiation(q)

sgp30ebbrE13.b1:
  • net radiation(q)
  • latent heat flux(e)
  • h(h)


Back To Table of Contents

DQRID : D040915.6
Start DateStart TimeEnd DateEnd Time
09/08/2004120009/15/20041930
Subject:
SGP/EBBR/E13 - AEM Failure, Fluxes Incorrect
DataStreams:sgp15ebbrE13.b1, sgp30ebbrE13.b1, sgp5ebbrE13.b1
Description:
The AEM failed.  Sensible and latent heat fluxes were incorrect, as well as gradient 
measurements.
Measurements:sgp15ebbrE13.b1:
  • Left air temperature(tair_l)
  • Right air temperature(tair_r)

sgp5ebbrE13.b1:
  • Temperature of bottom humidity sensor chamber(thum_bot)
  • top vapor pressure(vp_top)
  • top air temperature(tair_top)
  • Temperature of the top humidity chamber(thum_top)
  • bottom vapor pressure(vp_bot)
  • Bottom humidity(hum_bot)
  • Top humidity(hum_top)
  • bottom air temperature(tair_bot)

sgp30ebbrE13.b1:
  • Bottom humidity(hum_bot)
  • ratio of sensible/latent heat fluxes (Bowen ratio)(bowen)
  • bottom vapor pressure(vp_bot)
  • Temperature of bottom humidity sensor chamber(thum_bot)
  • Temperature of the top humidity chamber(thum_top)
  • latent heat flux(e)
  • h(h)
  • bottom air temperature(tair_bot)
  • top air temperature(tair_top)
  • Top humidity(hum_top)
  • top vapor pressure(vp_top)


Back To Table of Contents

DQRID : D050624.7
Start DateStart TimeEnd DateEnd Time
04/01/2001000003/31/20052100
Subject:
SGP/EBBR/E13 - Improved EBBR CR10 Program
DataStreams:sgp30ebbrE13.b1
Description:
Effective 20050331.2100, the EBBR.E13 CR10 program was revised to improve the quality of 
the primary measurements as follows:

1) An RMS procedure is used to determine max and min limits of acceptable soil heat flow.  
This is applied to the individual soil sets.  Measurements outside the limits are 
rejected and the measurements within the limits are used to calculate the average soil heat flow.

2) Max and min limits are used to determine incorrect values of net radiation, sensible 
heat flux (h), latent heat flux (e), and automatic exchange mechanism (AEM) signal.  If AEM 
signal is outside the limits, h and e are set to 999s.  If net radiation is outside the 
limits, h and e are set to 999s. If h or e are outside the limits, h and e are set to 999s.

Virtually no incorrect soil measurement will affect the primary measurements of h and e.

By setting h and e to 999s, it can be easily seen that the primary variables are 
incorrect; no other interpretation is possible.

Prior to 20050331, the improved CR10 program was NOT in effect.  DQRs have been submitted 
for known instances of incorrect soil measurements which affected the quality of the 
primary measurements of h and e.

Note: the DQR begin date is the begin date of the sgp30ebbrE13.b1 data stream.  The 
earlier version of the CR10 program was also used on previous EBBR datastream names (e.g. 
sgp30ebbrE13.a1).
Measurements:sgp30ebbrE13.b1:
  • average surface soil heat flow(ave_shf)
  • latent heat flux(e)
  • h(h)


Back To Table of Contents

DQRID : D051111.11
Start DateStart TimeEnd DateEnd Time
10/13/2003000007/22/20052359
Subject:
SGP/EBBR/E13 - metadata corrections
DataStreams:sgp15ebbrE13.b1, sgp30ebbrE13.b1, sgp5ebbrE13.b1
Description:
On 20050723, a series of metadata corrections and additions were completed.  These 
metadata changes apply to all EBBR.E13 data collected by ARM back to the installation of the 
instrument in September 1992.  Please see the current metadata for correct information.  
These changes do not affect data values or quality.

The changes are summarized below:
1) Update of "sensor location" information
2) Addition of installation dates for systems
3) Correction of soil type
4) Correction of soil moisture units (from "by volume" to "gravimetric")
Measurements:sgp15ebbrE13.b1:
  • base time(base_time)

sgp5ebbrE13.b1:
  • base time(base_time)

sgp30ebbrE13.b1:
  • base time(base_time)


Back To Table of Contents



END OF DATA