Data Quality Reports for Session: 111672 User: liuzheng Completed: 04/22/2008


TABLE OF CONTENTS

DQR IDSubjectData Streams Affected
D061011.3TWP/SMET/C2 - Reprocess: Tipping bucket rain gauge addedtwpsmet60sC2.b1
D070510.5TWP/SMET/C2 - Lower windspeed sensor questionabletwpsmet60sC2.b1
D070520.1TWP/SMET/C2 - Lower Wind Sensor Direction Incorrecttwpsmet60sC2.b1
D071219.1TWP/SMET/C2 - Lower Wind Speed Data Suspecttwpsmet60sC2.b1


DQRID : D061011.3
Start DateStart TimeEnd DateEnd Time
10/21/1998000011/29/20062014
Subject:
TWP/SMET/C2 - Reprocess: Tipping bucket rain gauge added
DataStreams:twpsmet60sC2.b1
Description:
A tipping bucket rain gauge was added to the TWP.C2 SMET suite of instruments on 20061129. 
Effective 20060926, two new variables (count and rain amount) were added to the end of 
the twpsmet60sC2.b1 datastream.  Between 9/26 and 11/29, the data for these two variables 
are filled with zeros.  Users should not use the data during this period as the zeros are 
not representative of the rain fall at the site.  When reprocessing of this datastream 
occurs these variables will be added for the 19981021-20060926 and data from 
19981021-20061129 will be filled with -9999 (missing).
Measurements:twpsmet60sC2.b1:
  • base time(base_time)


Back To Table of Contents

DQRID : D070510.5
Start DateStart TimeEnd DateEnd Time
04/05/2007000008/19/20072135
Subject:
TWP/SMET/C2 - Lower windspeed sensor questionable
DataStreams:twpsmet60sC2.b1
Description:
Lower wind speed sensor had degraded bearings.  This sensor was reporting as much as 0.4 
m/s lower values than the upper sensors when the winds were 2 m/s or below.  The sensor 
was replaced.
Measurements:twpsmet60sC2.b1:
  • Wind #2 speed maximum(wind2_spd_max)
  • Wind #2 speed vector average(wind2_spd_vec_avg)
  • Wind #2 speed maximum gust(wind2_spd_max_gust)
  • Wind #2 speed standard deviation(wind2_spd_sd)
  • Wind #2 speed arithmetic average(wind2_spd_arith_avg)
  • Wind #2 speed minimum(wind2_spd_min)


Back To Table of Contents

DQRID : D070520.1
Start DateStart TimeEnd DateEnd Time
05/11/2007000005/22/20070047
Subject:
TWP/SMET/C2 - Lower Wind Sensor Direction Incorrect
DataStreams:twpsmet60sC2.b1
Description:
Wind directions between lower and upper anemometers were displaced by approximately 45 
degrees from 05/10/2007 through 05/21/2007 when a new sensor was installed to replace a 
failing sensor.  The new sensor direction data incorrect.
Measurements:twpsmet60sC2.b1:
  • Wind #2 speed vector average(wind2_spd_vec_avg)
  • Wind #2 direction standard deviation(wind2_dir_sd)
  • Wind #2 direction vector average(wind2_dir_vec_avg)


Back To Table of Contents

DQRID : D071219.1
Start DateStart TimeEnd DateEnd Time
05/22/2007004808/19/20072150
Subject:
TWP/SMET/C2 - Lower Wind Speed Data Suspect
DataStreams:twpsmet60sC2.b1
Description:
The lower wind speed bearings appeared to be binding at speeds below 2 m/s as it did not 
compare well with the upper wind monitor.
Measurements:twpsmet60sC2.b1:
  • Wind #2 speed maximum(wind2_spd_max)
  • Wind #2 speed vector average(wind2_spd_vec_avg)
  • Wind #2 speed maximum gust(wind2_spd_max_gust)
  • Wind #2 speed standard deviation(wind2_spd_sd)
  • Wind #2 speed arithmetic average(wind2_spd_arith_avg)
  • Wind #2 speed minimum(wind2_spd_min)


Back To Table of Contents



END OF DATA