Start Date | Start Time | End Date | End Time | Data Quality Metric |
---|---|---|---|---|
01/13/2008 | 1400 | 01/23/2008 | 1817 | Incorrect |
Subject: | SGP/QCRAD/E4 - UPS failure |
DataStreams: | sgpqcrad1longE4.c1, sgpqcrad1longE4.c2, sgpqcrad1longE4.s1, sgpqcrad1longE4.s2 |
Description: | On Jan 13th approximately 1400GMT the UPS failed at E4. This affected both the global and tracker mounted instruments. The affected measurements are down_short_hemisp(PSP), down_short_diffuse(8-48) and direct_normal(NIP) measurements. The PSP down_short_hemisp measurement doesn't rely on the tracker but is power ventilated and is adversely affected by daytime solar heating when the ventilator power fails. Documented in instrument DQR D080212.3 |
Suggestions: | Don't use SW direct or diffuse data during these time periods. If "source_BestEstimate_down_short_hemisp" is 0, don't use Best Estimate GSW data. Note that fewer quality checks can be applied accurately to the BestEstimate data. |
Measurements: | sgpqcrad1longE4.c1: more
sgpqcrad1longE4.s1: more sgpqcrad1longE4.c2: more sgpqcrad1longE4.s2: more |