12/01/1995 | 0000 | 05/16/1996 | 1355 | Suspect |
Subject: | SGP/EBBR/E7 - Battery Voltage High |
DataStreams: | sgp15ebbrE7.b1 |
Description: | In March 1996 the battery voltage at E7 rose almost to 16 volts at times. Although not flagged by the qc checks, at times the voltage jumped from 13.5 to almost 16 volts within two 15 minute periods. The solar panel regulator may be at fault. The solar panel regulator was changed in the EBBR system. Regulator failure is almost always the cause of this problem. Note: The end date for this DQR was provided by the mentor at a later time. |